1. A Proportional Controller is used for
controlling temperature in melting process. Temperature set point is 750°C and temperature measuring tool range is 0 - 1000°C . Proportional
space is set at 15%. Pressure output range from controller is 20–100kN/m2 and pressure output rises when temperature
increases. If pressure output is set at
60 kN/m2 for temperature set point,
find
i. Temperature for pressure
output at 20kN/m2
ii. Temperature
for pressure output at 100kN/m2
2. In a process,a Proportional
Controller is used to control the liquid level in the boiler. The level is set at 8 meters and the level range is 1 to 14 meters. Proportional band is at 20%. The output current has a range
of 5–20mA. Determine:-
i.
The output level when current is 5
mA.
ii.
The output current at a level of 10
meters.
3. An
air to open valve on the inflow controls level in a tank. When the process is
at the set point the valve opening is 50%. An increase in outflow results in the valve opening increasing to a new steady state
value of 80%. What is resulting offset
if the controller PB is:
i)
80%
ii) 40%.
4. A temperature controller has the
following characteristic curve below:
The controller has a range of
100 0C to 400 0C. The set‐point is 250 0C.
Calculate:
i. The controller Proportional Band
ii. The controller Proportional Gain